Re: Clock Routing example "Destination Terminal" = "BoardClk"?

$
0
0

Hi,

The NI-Sync examples cover a number of modules. Therefore, some of the terminals listed in the examples may not be available on the PXIe-6674T.

BoardClk is only a valid terminal on the PXI-668x modules. This terminal is used internally by the Multi-device PXI_Clk10 Disciplining software. With the PXI-6683(H), this terminal can be used for single-device PXI_Clk10 disciplining as well.

Regards,
-Tyler